Case 1

Korea Airports Corporation

Case 2

Ulsan Airport

Case 3

Korea Expressway Corporation

Case 4

Nongshim Factory

Case 1

Korea Airports Corporation
(Gimpo Airport)

Remove the existing active filter and replace it with a hybrid transformer as a countermeasure to reduce harmonics.

Harmonic Reduction 45.8%,

Unbalance Improv. 98.3%,

PF Improv. 4.2%

Before

High-efficiency transformer + Active Filter (1,700kVA)

After

Hybrid Transformer (1,700kVA)

CategoryTransformerPower analysis results
HarmonicsUnbalancePF
BeforeHigh-efficiency Transformer15.311.80.95
AfterHybrid Transformer8.30.20.99
Decline rate(%)-45.898.34.2

Case 2

Ulsan Airport

Replacement with Hybrid Transformer to reduce harmonics in aviation lights and general power facilities

Aviation lights : Harmonic Reduction 68.6%,
Unbalance Improv. 24.5%, PF Improv. 2.4%
General power : Harmonic Reduction 50.0%,
Unbalance Improv. 67.7%, PF Improv. 2.9%

Before

High-efficiency transformer (Aviation lights & General power)

After

Hybrid Transforme (Aviation lights & General power)

CategoryUnitAviation lights (200kVA)General power (750kVA)
BeforeAfterInc/Dec (%)BeforeAfterInc/Dec (%)
ITHD%35.311.168.620.210.150.0
Unbalance%5.34.024.535.611.567.7
PF%90.192.32.495.598.32.9

Aviation lights -
Before Installation

Aviation lights -
After Installation

General power -
Before Installation

General power -
After Installation

Case 3

Korea Expressway Corporation

Installing Hybrid Transformer as a measures to reduce Harmonics in Tunnel LED Loads.

Harmonic Reduction 49.1%, Unbalance Improv. 1.0%

Before

High-efficiency transformer (200kVA)

After

Hybrid Transformer (200kVA)

CategoryHigh-efficiency transformer
(Before)
Hybrid Transformer
(After)
Reduction rate (%)
LED DimmingLED DimmingLED Dimming
15%50%100%15%50%100%15%50%100%
Real Power (kW)3465106305610111.813.84.7
PF0.850.950.980.900.970.995.92.11.0
V_THD(%)1.81.51.51.51.61.416.76.76.7
I_THD(%)17.18.35.713.973.118.715.745.6
I_TDD(%)6.54.85.343.52.738.527.149.1

Case 4

Nongshim Factory

Installing Hybrid Transformer as a measures to reduce Harmonics in Inverter Load

1,500kVA : Harmonic Reduction 47.1%, Unbalance Improv. 39.4%, PF Improv. 3.2%

1,000kVA : Harmonic Reduction 58.7%, Unbalance Improv. 51.7%, PF Improv. 10.8%

Before

High-efficiency transformer (4,500kVA)

After

Hybrid Transformer (4,500kVA)

CategoryUnit1,500kVA1,000kVA
BeforeAfterRate of Change (%)BeforeAfterRate of Change (%)
V_THD%1.41.121.41.31.115.4
I_THD%5.12.747.113.85.758.7
V_Unb%0.70.357.10.70.271.4
I_Unb%10.46.339.46.02.951.7
PF%86.489.23.273.381.210.8

Design/specification application examples

  • The design application and specifications are simple, minimizing the engineer’s working time.
  • We offer technical seminars and design resources to approximately 30 metropolitan-area design firms.

Application case 1

Application case 2