Installation Cases
Stable operating performance has been verified in various power environments, including industrial facilities, buildings, hospitals, and schools.
-
01 Korea Airports Corporation
Equipment Before Replacement After Replacement Transformer High-efficiency cast-resin transformer (1,700 kVA) + active filter Hybrid oil-immersed transformer (1,700 kVA) Active filter 60A x 4 units = 240A X 
분석 결과
Category Before Installation After Installation 개선효과 Harmonics (THD) 10.8 8.3 ▼ 23% Unbalance 11.5 2.7 ▼ 77% PF 0.95 0.99 △ 4% Harmonics
Before Installation
After Installation
Harmonics(단위 : %)
Unbalance
Before Installation
After Installation
Unbalance(단위 : %)
Harmonics
Before Installation
After Installation
PF(단위 : %)
- Harmonics Reduction ▼ 23%
- Unbalance Improvement ▼ 77%
- Power Factor Improvement △ 4%
-
02 Ulsan Airport
Equipment Before Replacement After Replacement 항공등화 High-Efficiency Cast-Resin 150kVA Hybrid Oil-Immersed 200kVA General Power High-Efficiency Cast-Resin 600kVA Hybrid Oil-Immersed 750kVA 
항공등화 설치 전 vs 설치 후
Before Installation After Installation
High-Efficiency Cast-Resin 150kVA
Hybrid Oil-Immersed 200kVA 일반동력 설치 전 vs 설치 후
Before Installation After Installation
High-Efficiency Cast-Resin 600kVA
Hybrid Oil-Immersed 750kVA 분석 결과
Category 단위 항공등화(200kVA) General Power(750kVA) Before Installation After Installation 증감율(%) Before Installation After Installation 증감율(%) Active power kW 97 122 △ 25.8 99 48 ▼ 51.5 ITHD % 35.3 11.1 ▼ 68.6 20.2 10.1 ▼ 50.0 Unbalance % 5.3 4.0 ▼ 24.5 35.6 11.5 ▼ 67.7 PF % 90.1 92.3 △ 2.4 95.5 98.3 △ 2.9 - 항공등화 : Harmonics Reduction ▼ 68.6%
- Unbalance Improvement ▼ 24.5%
- Power Factor Improvement △ 2.4%
- General Power : Harmonics Reduction ▼ 50.0%
- Unbalance Improvement ▼ 67.7%
- Power Factor Improvement △ 2.9%
-
03 Korea Expressway Corporation (LED load)
Equipment Before Replacement After Replacement Transformer High-Efficiency Oil-Immersed 200kVA Hybrid Oil-Immersed 200kVA Load Type LED LED 
분석 결과
Category Before Replacement (High-Efficiency Transformer) After Installation (Hybrid Transformer) Reduction(%) LED Dimming LED Dimming LED Dimming 15% 50% 100% 15% 50% 100% 15% 50% 100% Voltage(V) 376 375 375 377 377 377 △ 0.3 △ 0.5 △ 0.5 Current(A) 62 105 166 51 89 156 ▼ 17.7 ▼ 15.2 ▼ 6.0 유효전력(kW) 34 65 106 30 56 101 ▼ 11.8 ▼ 13.8 ▼ 4.7 피상전력(kVA) 40 68 108 33 58 102 ▼ 17.5 ▼ 14.7 ▼ 5.6 Power Factor(PF) 0.85 0.95 0.98 0.90 0.97 0.99 △ 5.9 △ 2.1 △ 1.0 V_THD(%) 1.8 1.5 1.5 1.5 1.6 1.4 ▼ 17.5 △ 6.7 ▼ 6.7 I_THD(%) 17.1 8.3 5.7 13.9 7.0 3.1 ▼ 18.7 ▼ 15.7 ▼ 45.6 I_TDD(%) 6.5 4.8 5.3 4.0 3.5 2.7 ▼ 38.6 ▼ 27.1 ▼ 49.1 - Harmonics Reduction ▼ 49.1%
- Power Factor Improvement △ 1.0%
-
04 Major Corporate Plant (motors / inverter loads)
Equipment Before Replacement After Replacement 비고 Transformer High-Efficiency Oil-Immersed 4대(4,500kVA) Hybrid Oil-Immersed 4대(4,500kVA) 인버터 제어 동력설비에 Hybrid 변압기를 적용한 사례 Load Type General Power, Inverter General Power, Inverter 
Hybrid Oil-Immersed 1,000kVA
Hybrid Oil-Immersed 1,000kVA
Hybrid Oil-Immersed 1,000kVA
Hybrid Oil-Immersed 1,500kVA 분석 결과
Category 단위 1,500 kVA 1,000 kVA Before Replacement After Installation 증감율(%) Before Replacement After Installation 증감율(%) V_THD % 1.4 1.1 ▼ 21.4 1.3 1.1 ▼ 15.4 I_THD % 5.1 2.7 ▼ 47.1 13.8 5.7 ▼ 58.7 V_Unb % 0.7 0.3 ▼ 57.1 0.7 0.2 ▼ 71.4 I_Unb % 10.4 6.3 ▼ 39.4 6.0 2.9 ▼ 51.7 PF % 86.4 89.2 △ 3.2 73.3 81.2 △ 10.8 - 1,000kVA : Harmonics(ITHD) Reduction ▼ 58.7%
- Unbalance (IUnb) Improvement ▼ 51.7%
- Power Factor Improvement △ 10.8%
- 1,500kVA : Harmonics(ITHD) Reduction ▼ 47.1%
- Unbalance (IUnb) Improvement ▼ 39.4%
- Power Factor Improvement △ 3.2%
-
05 J Hotel (lighting / heating load)
Equipment Before Replacement After Replacement Transformer High-efficiency cast-resin transformer (400kVA) Hybrid cast-resin transformer (400kVA) Load Type Lighting & Power Lighting & Power 
분석 결과
Category 단위 Before Replacement After Installation 증감율 (%) V_THD % 1.16 1.10 ▼ 5.2 I_THD % 23.39 16.77 ▼ 30.1 PF % 93 96 △ 3.0 - Harmonics(ITHD) Reduction ▼ 30.1%
- Power Factor Improvement △ 3.0%
-
06 Incheon Environment Corporation (concentration equipment)
Equipment Before Replacement After Replacement Transformer High-efficiency cast-resin transformer (1,000kVA) Hybrid cast-resin transformer (1,000kVA) Load Type Concentration Equipment Concentration Equipment 
분석 결과
Category 단위 Before Replacement After Installation 증감율 (%) V_THD % 1.1 0.8 ▼ 29.3 I_THD % 5.4 3.6 ▼ 33.4 PF % 94 94 - - Harmonics Reduction ▼ 33.4%
-
07 Dongwha Enterprise (GHG reduction)
Power Quality Diagnostic Results
After replacement with Hybrid Transformers, voltage and current harmonics decreased, and overall power efficiency improved together with power factor.
- Average harmonic reduction of 5–7% per transformer and reduced reactive power losses led to lower power consumption.
Transformer Voltage / Frequency / Power Factor Load Ratio (%) Voltage Harmonics (%) Current Harmonics (%) Current Distortion (%) TR #11 인정 / 정상(98%) 50.8 ▼ 3.38 ▼ 7.73 ▼ 5.58 TR #12 인정 / 정상(98%) 36.7 ▼ 2.58 ▼ 7.53 ▼ 5.93 TR #13 인정 / 정상(90%) 60.1 ▼ 1.52 ▼ 1.81 △ 0.18 Diagnostic Result Average current harmonic reduction rate 5.69% Savings Calculation Formula : Transformer capacity (kVA) × THDF reduction rate (%) × load ratio (%)
Savings versus post-replacement power consumption
Power-use period: Aug. 2023 – Oct. 2023
Transformer Power savings(MWh/년) Electricity cost savings (KRW million/year) 절감률(%) 투자비용(KRW million) 투자회수기간(Year) TR #11 420.9 54.7 7.63 83.93 1.5 TR #12 345.9 45.0 5.56 83.93 1.9 TR #13 93.5 12.2 1.02 83.931 6.9 Diagnostic Results 860.4 111.9 3.7 252 2.3 Electricity charge = Power consumption × KRW 130/kWh / power-use period (28 days/month × 12 months)
- Converted to annual savings based on the actual operating load before replacement → approximately 3.7% reduction in annual electricity consumption versus before replacement
- Payback period: 2.3 years based on the same operating load as before replacement
-
08 Design Application Case
Hybrid Transformers are clearly specified in single-line diagrams and technical specifications, making them easy and clear to apply from the design stage. They can be reflected directly in drawings and specifications without additional design work, improving efficiency and consistency.


-
Lighting, Power BANK (retail / neighborhood facilities)
MOLD TR (Hybrid Transformer) - 3Φ 500 kVA
-
Primary Voltage : 22.9kV
Secondary Voltage : 380V / 220V


-
TR#3
General Power -
3Φ -4W, 60Hz
22.9kV / 380 / 220V 0V 1,500kVA - Hybrid Transformer
-
Lighting, Power BANK (retail / neighborhood facilities)